Cuarto año Lesson 10 of 12 · about 14 min
Protective relaying concepts
What you’ll learn
- How a relay, its CTs and PTs, and a breaker work together: sense, decide, trip.
- What the common device numbers on a single-line mean — 50, 51, 87, 27, 59, 86, 52.
- How a differential relay tells an internal fault from a heavy through-fault.
- Why a CT secondary is never opened under load, and why lockout relays are reset by hand.
Before this: Overcurrent protection and coordination · Available fault current
A protective relay watches a scaled-down copy of the current and voltage, decides whether something is wrong, and closes a contact that trips a breaker. It never interrupts the fault itself. Sensing is done by instrument transformers, deciding by the relay, and interrupting by the breaker — and a failure in any one of the three means no protection.
The eyes: CTs and PTs
A relay cannot connect to thousands of amps or thousands of volts. A current transformer (CT) puts out a small current in proportion to the primary current — a 600:5 CT gives 5 A when 600 A flows. A potential transformer (PT, or VT) steps the voltage down to a standard low value. The relay then works on those copies.
Never open a CT secondary with current in the primary. A CT is built to drive its current into a near short. Open the loop and it tries anyway — the secondary voltage climbs until something breaks down: the insulation, an arc, or you. Short the secondary with its shorting block before you disconnect anything on it. The transformer basics page explains why.
The brain: device numbers
| Number | Function | What it is watching for |
|---|---|---|
| 50 | Instantaneous overcurrent | A heavy fault close by — trip with no intentional delay |
| 51 | Time overcurrent | Overcurrent that follows an inverse curve: more current, faster trip |
| 50N / 51N / 51G | Ground (residual or neutral) overcurrent | Current returning by a path other than the phase conductors |
| 87 | Differential | Current in ≠ current out of a protected zone |
| 27 / 59 | Under / overvoltage | Loss or sag of supply; voltage too high |
| 86 | Lockout relay | Holds breakers tripped until reset by hand |
| 52 | AC circuit breaker | The muscle — opens the power circuit |
How a differential relay thinks
Real transformer differential relays have to allow for the turns ratio, the 30° shift through a delta-wye bank and the inrush when the transformer is energized, which is why their settings and CT connections are an engineering job. The idea underneath is still “in should equal out”.
Worked: what the relay sees through a CT
- A feeder has 600:5 CTs. Ratio = 600 ÷ 5 = 120.
- Load current 360 A: the relay sees 360 ÷ 120 = 3 A.
- A fault of 9,600 A: the relay sees 9,600 ÷ 120 = 80 A — for the few cycles until it trips. That is why CT secondary wiring and test blocks are built heavy.
- A relay set (by the engineer) to pick up at 4 A secondary is picking up at 4 × 120 = 480 A primary.
The muscle: the trip circuit
The relay’s trip contact energizes the breaker’s trip coil, usually from a station battery so it works when the AC is collapsing. A lockout relay (86) often sits between them: once it operates it holds every breaker it controls open until someone resets it by hand. That is deliberate — after an internal fault, re-energizing automatically is the wrong answer. Test switches let technicians isolate the trip circuit and the CTs safely while they test.
En la obra
Tips
- Learn to read the device numbers on a single-line; they tell you what protects what.
- Short CT secondaries at the test block before you touch the wiring downstream — every time.
- Check the trip circuit is healthy (many panels have a trip-circuit monitor light). A relay with no trip path is decoration.
- Record relay targets (the flags or event log) before anyone resets anything; they are the evidence.
Common mistakes
- Opening a CT circuit under load.
- Resetting an 86 lockout without finding out why it operated.
- Rolling a CT’s polarity (swapping the secondary leads) — a differential scheme will then trip on load.
- Changing relay settings to stop nuisance trips instead of finding the cause.
- Confusing the 52 (the breaker) with the relay that tells it to open.
Check yourself
-
1.A protective relay detects a fault. What does it actually do about it?
A relay is the brain, not the muscle. It watches current and voltage through CTs and PTs, decides, and operates a trip contact. The breaker is what opens the power circuit — which is why a relay with a dead trip circuit protects nothing.
-
2.In the standard device numbering, what is the difference between a 50 and a 51 element?
50 trips with no intentional delay above its pickup — for heavy faults close by. 51 follows an inverse time curve, so modest overloads take longer and big faults trip quickly. Most feeder relays have both.
-
3.A differential (87) relay on a transformer compares the current going in with the current coming out. When does it trip?
For a fault outside the zone, the same current flows in and out, the CT currents cancel and the relay stays put however large the current. A fault inside the zone makes in ≠ out, and the difference operates the relay. That makes it fast and selective.
-
4.You need to disconnect a meter wired to a CT secondary while the primary is carrying load. What do you do first?
An open CT secondary with primary current flowing can develop a very high voltage — dangerous to you and to the insulation. Always short the secondary first, then work on the downstream device.
-
5.What is the job of a PT (potential or voltage transformer) in a relaying scheme?
Relays and meters cannot connect directly to medium or high voltage. A PT gives them a scaled-down copy of the voltage, just as a CT gives them a scaled-down copy of the current.
-
6.A 27 element operates on undervoltage and a 59 on overvoltage. Where might a 27 be used?
Undervoltage relays catch loss or sag of supply — used to drop motors so they do not all restart together, or to signal a transfer switch to start the generator.
-
7.A lockout relay (86) has tripped after a transformer differential operation. Why is it designed so that it must be reset by hand?
An 86 trips and holds the breakers open until a person resets it. An internal transformer fault re-energized automatically could turn damage into destruction. The lockout forces the question “why did it trip?” to be answered first.
Preguntas frecuentes
Why use relays when breakers already have trip units?
Low-voltage breakers do have built-in trip units, and for most building work that is all there is. Above that — medium-voltage switchgear, large transformers, generators, utility ties — the breaker is just a switch that can interrupt a fault, and separate relays fed by CTs and PTs decide when to open it. Relays can do things a trip unit cannot: compare currents in two places, look at voltage and frequency, and coordinate across a whole system.
What do the device numbers mean?
They are a standard shorthand (IEEE/ANSI C37.2) used on single-lines and relay panels worldwide: 50 instantaneous overcurrent, 51 time overcurrent, 50/51N or 51G for the ground versions, 87 differential, 27 undervoltage, 59 overvoltage, 81 frequency, 86 lockout, 52 the circuit breaker itself. Seeing “51” on a drawing tells you the function, whatever make of relay is in the panel.
Who sets the relays?
The settings come from a protection engineer’s coordination study. Electricians and relay technicians install, wire, test and put those settings in; they do not choose them. Changing a relay setting because it “keeps tripping” is how coordination gets destroyed.
Ver también
- Transformer basics — the CT warning, in full
- Overcurrent protection and coordination — time-current curves
- Available fault current
- Reading commercial and industrial prints — device numbers live on single-lines
- Emergency and standby power
¿Ve algo incorrecto en esta página? Repórtelo
Gracias — su reporte fue enviado.
No se pudo enviar. Vuelva a intentarlo más tarde.
Avisos de herramientas que le sirven — por correo, opcional
Deje su correo y marque la casilla para recibir un aviso breve, como máximo cada dos semanas, sobre herramientas, ejercicios y diagramas que encajan con lo que ha estado estudiando — aquí y en bentright.com y fieldcalc.net. Es la misma lista para los tres, se sale con un clic y no se envía nada hasta que confirme desde su bandeja de entrada.