Esta página aún no está traducida del todo. Lo que falta se muestra en inglés por ahora. Leer la versión en inglés →

Motor control · lesson 6 of 12

Jogging (inching)

Jogging means running a motor only while a button is held. Every jog circuit does the same thing: it takes the seal-in out of the path. Here are two ways to do it.

A Run/Jog selector

The simplest version puts a selector switch contact in series with the seal-in. In Run the contact is closed and the circuit latches as normal. In Jog it is open, so the seal-in branch can never complete and Start becomes a hold-to-run button.

Selector marcha/impulso

X1X21ParoArranqueMSS (Marcha)OLM1Arrancador del motor

Active JavaScript para presionar los botones y hacer funcionar este circuito.

Haga esto

El selector está en la rama del contacto de retención. En Impulso, abre esa rama.

Impulso con un relevador de control

A better arrangement uses a small control relay, CR, to do the latching. Run and Stop latch CR on rung 1. The starter M on rung 2 is fed by either a CR contact or the Jog button — and nothing on rung 2 seals anything in. So a jog can never turn into a run by accident.

Impulso con un relevador de control

X1X21ParoMarchaCRCR1, 2Relevador de marcha2CRImpulsoOLMArrancador del motor

Active JavaScript para presionar los botones y hacer funcionar este circuito.

Haga esto

Un relevador de marcha (CR) hace la retención; el arrancador M solo sigue a CR o al botón de Impulso.

You will still see the "Jog button with an NC contact in the seal-in branch" circuit on older machines. It works most of the time — but it depends on the button's NC contact reclosing after the starter's seal-in has dropped out, and a quick jab can beat it. A motor that runs away when someone only meant to nudge it is the reason the relay version exists.

En la obra

Jogging exists so somebody can inch a machine into position. Everything that goes wrong with it comes from the seal-in getting back in when it should not.

Common mistakes

  • A jog contact that breaks the seal-in too late. On a selector-type jog the contact has to be open before the coil pulls in, or the starter seals itself and the machine runs away from the operator.
  • Jogging with the selector left in Run. The button then latches the motor instead of inching it. Label the selector and put the pilot light where the operator actually stands.
  • Jogging a starter it was not chosen for. Repeated inching is hard duty: heavy inrush over and over, with no running time to cool. Whether a given contactor is rated for it is a manufacturer question, and the answer is on their sheet.
  • Using a control relay's NC contact for the seal-in break without checking its timing — a slow relay gives the seal-in a moment to catch.

On a real panel

  • The control-relay version is the safer pattern: the relay decides, so the seal-in path is broken by a contact that is already open before Start does anything.
  • A jog station is usually near the machine, not at the panel — that is the whole point. Its enclosure and cord entry have to survive where it lives.
  • Expect guards, interlocks or a hold-to-run device around a jog function on production machinery. The machine's own standard, not this page, says what is required.

Prove it before you leave

  1. In Jog, press and release the button ten times with the motor disconnect open. The starter must drop out every single time the button is released.
  2. In Run, press and release once. It must seal in and hold.
  3. Switch from Run to Jog while it is running. Decide with the machine's owner what should happen, then make sure that is what does.
  4. Only then close the disconnect and inch the real machine, with your hand on Stop.

Preguntas frecuentes

What does jog mean in motor control?

Running a motor only while a button is held, with no seal-in — to inch a machine into position, line up a belt or thread material. Let go and it stops.

Why use a control relay for jogging?

The quick way — putting a jog button’s NC contact in the seal-in branch — can race: if that NC contact recloses before the starter’s seal-in has dropped out, the motor latches and keeps running. A separate run relay means the jog path simply has no latch in it.

¿Ve algo incorrecto en esta página? Repórtelo

Incluiremos esta página y los números que usted escribió. Leemos cada reporte, pero no podemos responder.

Gracias — su reporte fue enviado.