Start/stop and the seal-in
This is the circuit every other motor control circuit is built from: a normally closed Stop, a normally open Start, and a seal-in contact in parallel with Start. Press Start and the coil pulls in; the coil closes its own seal-in; let go and it stays in; press Stop and it drops out for good. There is also a stand-alone start/stop diagram with the power rung drawn out and the three classic wiring mistakes.
Arranque/paro a tres hilos con retención
Active JavaScript para presionar los botones y hacer funcionar este circuito.
Haga esto
El peldaño 1 es el control. Los peldaños 2 y 3 son luces piloto accionadas por contactos de M.
Trace rung 1 out loud
- From X1, through Stop. It is normally closed and nobody is pressing it, so go through.
- A fork. Top branch: Start, open. Bottom branch: the M seal-in, open because M is not energized. Neither goes through — the coil is dead.
- Press Start. The top branch closes: through it, through the overload contact (closed unless tripped), into coil M, to X2. M pulls in.
- Every M contact moves. The seal-in closes. The Running light's NO contact closes; the Stopped light's NC contact opens.
- Let go of Start. The top branch opens — but the bottom branch is now closed. Still a complete path. That is the seal-in.
- Press Stop. The rung is broken before the fork, so both branches lose their supply. M drops out, the seal-in opens, and letting go of Stop changes nothing: the fork is open again.
Meter it
The last step of the lab hands you a meter with the black lead on X2. Every dot on the drawing is a place you can put the red lead. You read control voltage wherever the point connects back to X1, and 0 V wherever something between X1 and the point is open. On a real panel that is exactly how you find a problem: start at X1 and move along the rung until the voltage disappears. The part you just stepped over is open. The troubleshooting lesson is built around it.
En la obra
Every panel you ever open has this rung in it somewhere. Knowing the three ways it goes wrong means most start/stop calls are solved before you take the meter out of the pouch.
Common mistakes
- The seal-in landed across Stop. Starts perfectly, never stops. The seal-in goes across Start and nothing else.
- A normally open button fitted as Stop. It has to break a path that is already carrying. Closed for Stop, open for Start — and a closed Stop also fails safe when its wire breaks.
- The overload contact left out of the rung. The overload's only way to stop the motor is to open this rung. Leave its contact out and tripping it does nothing.
- Landing the seal-in on the wrong auxiliary. Starters carry both NO and NC auxiliaries. The seal-in must be a normally open one that closes when the coil pulls in; an NC will latch the circuit off instead.
- Jumpering the Stop button "just to test". Jumpers get left in. If you must, put one wrap of tape on the panel door as a reminder and take it off before you leave.
On a real panel
- The fork is usually a terminal strip point, not a physical junction. Two wires under one terminal is the parallel branch.
- Control power often comes from a transformer inside the enclosure, so the motor disconnect does not kill it. Prove both.
- An e-stop or pull-cord is wired exactly like a Stop: in series, ahead of the fork, normally closed.
- Pilot lights usually hang off the starter's own auxiliaries — a NO contact for Running, an NC for Stopped, so exactly one is lit.
Prove it before you leave
- Energise the control with the motor disconnect still open. Start, release, Stop. It must seal in, hold, drop out, and stay out.
- Hold Stop in and press Start. Nothing may happen.
- Trip the overload by hand. The starter must drop, and must not pick itself back up on reset.
- Only then close the motor disconnect, bump it, and check rotation before anything is coupled.
Preguntas frecuentes
What is a seal-in contact?
A normally open contact of the motor starter wired in parallel with the Start button. When the coil pulls in, the contact closes and keeps the coil fed after Start is released. It is also called a holding contact, auxiliary contact or maintaining contact.
Why is the Stop button normally closed?
Because it has to break a path that is already carrying current. A normally closed button in series lets current through until it is pressed. It also fails safe in one important way: if a wire to the Stop button breaks, the circuit stops rather than becoming unstoppable.
Why do pilot lights use contacts instead of wiring across the motor?
A contact off the starter tells you the starter is pulled in. On a control print you usually see a NO contact for a Running light and a NC contact for a Stopped light, so exactly one is on at a time.
¿Ve algo incorrecto en esta página? Repórtelo
Gracias — su reporte fue enviado.
No se pudo enviar. Vuelva a intentarlo más tarde.
Avisos de herramientas que le sirven — por correo, opcional
Deje su correo y marque la casilla para recibir un aviso breve, como máximo cada dos semanas, sobre herramientas, ejercicios y diagramas que encajan con lo que ha estado estudiando — aquí y en bentright.com y fieldcalc.net. Es la misma lista para los tres, se sale con un clic y no se envía nada hasta que confirme desde su bandeja de entrada.