First year Lesson 10 of 14 About 15 min

Boxes, devices and terminations

What you’ll learn

  • How to strip a conductor cleanly and why a nick matters.
  • The screw-terminal loop, the back-wire clamp and the push-in hole — and which to trust.
  • Wire connectors and pigtails, and why the package instructions are part of the job.
  • Why a loose connection gets hot, with the arithmetic.
  • What box fill is and where the numbers for it come from.

Most electrical failures you will ever be called to are not in the middle of a wire — they are at the ends, where a conductor meets a terminal or another conductor. A good termination has full metal contact, holds its grip for decades and doesn’t damage the conductor getting there. This lesson is the workmanship that makes that happen.

Stripping

Strip with a stripper sized to the gauge — the hole cuts the insulation and stops at the copper. Take off only what the terminal needs: devices print a strip gauge on the back, and connectors give a strip length on the package. Check the copper afterwards. A nick or ring cut means less metal at that point, a weak spot that cracks when it is bent, and a small hot spot under load. Cut it off and strip again.

The screw terminal

✓ clockwise tightening pulls it in ✗ counter-clockwise tightening pushes it out
The screw turns clockwise to tighten (arrows). Hook the conductor the same way and the screw head drags the loop in under itself; hook it the other way and the screw shoves it out.

Bend a hook about three-quarters of the way round the screw, clockwise, with the insulation stopping just short of the screw head. Close the hook with your pliers so it hugs the screw, then tighten. One conductor per screw unless the terminal is marked for more — if you need to feed through, splice and bring a short pigtail to the device.

Many devices also offer a back-wire clamp: a straight-stripped conductor goes in a hole and the terminal screw clamps a plate onto it. That is a strong connection and often allows two conductors. The push-in (back-stab) hole, with no screw, is a spring contact — it works, but it grips a much smaller area and is a common source of loose connections.

Splices and connectors

Twist-on connectors, push-in connectors, lever connectors, crimp sleeves and split-bolts all do the same job: hold conductors in solid metal contact. Each one is rated for a range of conductor sizes and combinations, and some for copper only. The rating and the installation steps are on the package — follow them, because the listing only covers the connector installed the way the maker tested it. Finish every splice with a tug test on each conductor.

Why a loose connection gets hot

A tight joint has almost no resistance. A loose one has a little — and the load current flows through it, making heat by P = I² × R. That heat oxidises the metal, which raises the resistance, which makes more heat. It is a runaway, and it ends in a melted device or a fire.

Worked: the same terminal, tight and loose

  1. A receptacle feeds 15 A of load downstream through its terminals.
  2. A good terminal, 0.002 Ω (a practice number): P = 15² × 0.002 = 225 × 0.002 = 0.45 W. Nothing you’d feel.
  3. Worked loose to 0.2 Ω: P = 225 × 0.2 = 45 W — like a small soldering iron, sealed in a plastic box in a wall.
  4. The voltage lost there: V = I × R = 15 × 0.2 = 3 V. The lights downstream barely notice, so nobody knows until it scorches.

Torque

“Tight” is not a number. Terminals on breakers, panels, lugs and many devices carry a specified torque on the equipment or in the instructions, and both codes expect it to be met. Too loose and you get the heat above; too tight and you can crush strands, crack the terminal or cold-flow aluminium. Use a torque screwdriver or wrench and the value on the label.

Boxes and box fill

Every box has a volume (stamped inside or listed by the maker) and every conductor, device, clamp and fitting inside takes an allowance of that volume. Box fill is the sum that proves they fit — and there has to be room left to fold everything in without damaging it. The allowances per conductor size and the counting rules are in the CEC (CSA C22.1) or the NEC, whichever you work under; they differ between the two, so use your own book. Do the sum when you pick the box, not when the device won’t go in.

The habit

Pick the box from the count on the plan before rough-in: how many cables, what size, what device. A deeper box costs cents; changing a box after drywall costs an hour.

Try one: 20 A through a 0.1 Ω joint

P = 20² × 0.1 = 400 × 0.1 = 40 W. Double the current and the heat goes up four times: at 10 A the same joint makes 10 W.

Sur le chantier

Tips from the job

  • Use the strip gauge on the back of the device. Too short and the clamp bites insulation; too long and bare copper shows outside the terminal.
  • Make the ground connection first when you install a device, and take it off last when you remove one.
  • Fold conductors neatly into the back of the box in a zig-zag before you push the device in — don’t let the device crush them.
  • Use a torque screwdriver on terminals that list a torque. It is quicker than a callback for a burnt receptacle.
  • Leave enough free conductor in the box to work on it later. How much the code wants is in your book.

Common mistakes

  • Wrapping the conductor counter-clockwise, so the screw pushes it out as it tightens.
  • Relying on back-stab (push-in) holes on a receptacle that feeds other receptacles. They carry the downstream load through a small spring contact.
  • Two conductors under a screw made for one.
  • Cramming a box. If the device fights you going in, the box fill sum probably says it’s too full.
  • Landing aluminium on a terminal not marked for it.

Check yourself

7 questions. Tap an answer — it is marked straight away and the reason opens under it. Get 80% or better and the lesson is ticked off on the year page.

Not started yet.

  1. Which way should a conductor wrap around a terminal screw?

    Answer and why

    A. Clockwise, so tightening the screw pulls the loop in under the head. Counter-clockwise and the screw pushes the loop out as it tightens.

  2. Where do you find how tight a terminal should be?

    Answer and why

    B. Terminals have a specified torque, and it is on the device, the equipment or the instructions. A torque screwdriver or wrench is how you know you hit it.

  3. How do you work out whether a box has room for its conductors and devices?

    Answer and why

    C. Box fill is a calculation: the box’s volume against the allowances the CEC or NEC gives for each conductor, device, clamp and fitting. The numbers are in the book — do the sum before you rough in.

  4. A stripped conductor has a nick in the copper. What is the problem?

    Answer and why

    C. The nick reduces the area — more resistance right there, and a place where the conductor will crack when it is bent. Re-strip it.

  5. A loose terminal has 0.2 Ω of resistance and carries 15 A. How much heat is made at the terminal?

    Answer and why

    B. P = I² × R = 15 × 15 × 0.2 = 225 × 0.2 = 45 W, in a space the size of a screw head.

  6. Can you put two conductors under one screw terminal?

    Answer and why

    C. Most device screw terminals are for one conductor. Some are made for two (a back-wire clamp often is) and say so. When in doubt, splice and pigtail.

  7. What does a twist-on or push-in wire connector’s packaging tell you?

    Answer and why

    B. Every connector is rated for a range of conductor sizes and combinations and has install instructions (strip length, whether to pre-twist). Follow them — that is what the listing depends on.

Questions fréquentes

Are back-stab (push-in) connections allowed?

Many devices are listed with push-in holes for certain conductor sizes, so they are generally allowed where the device’s listing and your code permit. Plenty of electricians avoid them anyway, because the small spring contact has less grip than a screw or clamp and is a common source of loose, hot connections. A back-wire clamp (the screw-tightened hole) is a different thing and is usually a very good connection.

Do I need to pre-twist conductors before a twist-on connector?

Follow the connector maker’s instructions — some say pre-twisting is optional, some recommend it. What matters is the finished joint: every conductor fully in, no bare copper showing below the skirt, and a firm tug on each conductor doesn’t pull it out.