Fourth year Lesson 2 of 12 · about 16 min

VFD parameters and troubleshooting

What you’ll learn

  • The handful of parameters you set on every drive, and where each value comes from.
  • How accel and decel ramps work, and why a fast stop trips on overvoltage.
  • What the four common trips — overvoltage, overcurrent, ground fault, undervoltage — usually mean.
  • A safe order for troubleshooting a drive, including how to insulation-test the motor without killing the drive.

Before this: How a VFD works

A drive only knows what you tell it. Most drive problems are either a parameter that does not match the motor or the job, or the drive correctly tripping to tell you about a problem somewhere else — in the supply, the cable, the motor or the load. The fault code is the drive’s best guess at which. Learn what each common one means and you fix most drives without changing a part.

The parameters you set on every drive

ParameterWhere the value comes fromWhy it matters
Motor voltage, frequency, rpmMotor nameplateSets the V/Hz pattern and the slip estimate
Motor full-load currentMotor nameplateThe drive’s electronic overload protects the motor from this
Min / max frequencyThe process and the machine makerKeeps pumps above their minimum and machines below their safe speed
Accel / decel timeThe load: how heavy, how fast it must respondToo short trips; too long makes the process sluggish
Start / speed sourceThe control designKeypad, terminals, 4–20 mA or network — the drive must listen to the right one
Stop modeThe loadRamp to stop or coast; a fan usually coasts, a conveyor ramps

Then run the drive’s auto-tune if it has one and the motor is safe to turn. Write your settings down, or save them to the keypad — the next person to replace that drive will thank you.

Ramps, and where the energy goes

60 0 Hz accel run decel bus rises here time →
Accel pulls energy from the supply. Decel faster than the load would coast and the motor becomes a generator, pushing energy back into the DC bus — the cause of most overvoltage trips.

Accel and decel times are nearly always set as the time for the full range, 0 to base frequency. A 10 s accel on a 60 Hz drive is a ramp of 6 Hz per second, whatever speed you are actually going to.

Worked: reading the ramp

  1. Accel is set to 12 s for 0–60 Hz: the ramp is 60 ÷ 12 = 5 Hz/s.
  2. The speed reference is 45 Hz. Time to get there: 45 ÷ 5 = 9 s.
  3. Decel is set to 3 s. Stopping from 45 Hz takes 45 ÷ (60 ÷ 3) = 45 ÷ 20 = 2.25 s.
  4. If that 2.25 s stop trips on overvoltage, the load cannot be slowed that fast without braking: lengthen decel (try 8–10 s), or fit the braking resistor the drive maker specifies.

The four trips you will see most

TripWhat the drive sawUsual causes
OvervoltageDC bus too highDecel too short; overhauling load (a load that drives the motor); high or surging supply
OvercurrentOutput current too high, too fastAccel too short; jammed or heavy load; short in the cable or motor; wrong motor data
Ground faultCurrent leaking to ground on the outputDamaged cable insulation; water in the motor or terminal box; failed winding
UndervoltageDC bus too lowSupply sag (a big motor starting nearby); lost phase; loose line connection; blown input fuse

Two more you will meet: drive overtemperature (blocked filters, a dead heatsink fan, a hot room) and motor overload (the load really is too heavy for too long — or the FLA parameter is wrong). The trip tells you where to look, not what to replace.

A safe order to work in

  1. Read before you reset. Write down the fault code, the fault history and what the machine was doing.
  2. Check the supply. Line voltage on all three phases at the drive input, and the DC bus against 1.35 × line.
  3. Check the load. Does it turn freely? Has anything changed in the process?
  4. Check the parameters against the motor nameplate and the job.
  5. Test the motor and cable — isolated. Lock out, wait, verify the bus is dead, lift the motor leads at the drive, then insulation-test the cable and motor. Never meg through the drive.
  6. Only then suspect the drive.

On the job

Tips

  • Photograph or save the parameter list the day a drive is commissioned.
  • A trip that only happens at one point in the cycle (starting, stopping, one speed) is almost always a setting or the load, not the drive.
  • Measure motor current with a clamp on the drive output and compare it to the nameplate FLA.
  • If the bus reads low with one input phase missing, the drive may still run lightly loaded and trip under load — check all three input fuses.

Common mistakes

  • Resetting three times and calling it fixed.
  • “Fixing” an overcurrent trip by raising the current limit instead of finding the jam.
  • Meggering the motor with the leads still on the drive output.
  • Setting FLA from the drive rating instead of the motor nameplate.
  • Working on the output terminals because the display went dark — the bus can still be charged.

Check yourself

0 right of 0 answered 8 questions · pick one answer each

  1. 1.A drive runs a heavy flywheel fine but trips on overvoltage every time it is told to stop. The most likely cause?

  2. 2.A fan drive trips on overcurrent partway through every start, never while running. What do you look at first?

  3. 3.You need to insulation-test (megger) a motor fed from a drive. What must you do first?

  4. 4.Why do you enter the motor’s nameplate full-load current into the drive?

  5. 5.An outdoor pump drive starts tripping on ground fault after a storm. What is the sensible first suspicion?

  6. 6.A drive is set to accelerate from 0 to 60 Hz in 12 s. How long does it take to reach 45 Hz?

  7. 7.A drive trips on undervoltage only when a large motor elsewhere in the plant starts across the line. The drive is probably…

  8. 8.A drive has tripped. What is the most useful first step before pressing reset?

Questions people ask

What does auto-tune actually do?

It makes the drive measure the motor it is connected to — winding resistance, inductance and sometimes magnetising current — so its motor model matches reality. Sensorless-vector control depends on that model. A static auto-tune does it with the shaft still; a rotating one spins the motor, so the load must be safe to turn or uncoupled. Follow the drive manual.

Do I still need a separate overload relay with a drive?

Most drives include an electronic motor overload that, set correctly from the nameplate, protects a single motor. Where one drive feeds several motors, each motor usually needs its own overload. Whether the drive’s protection is acceptable for your installation is a code-book and drive-listing question.

What is a braking resistor for?

When a motor is slowed faster than friction would stop it, it regenerates energy into the DC bus. With nowhere to go, the bus voltage rises until the drive trips on overvoltage. A braking transistor and resistor switch that energy into heat, so the drive can stop a heavy load quickly without tripping.