Fourth year Drives · tool
VFD frequency and speed calculator
Enter the motor’s nameplate base frequency, speed and voltage. Then give a drive frequency to get the shaft speed, or a target speed to get the frequency to set — with the V/Hz and the voltage the drive will put out.
- Estimated shaft speed—
- Frequency to set—
- Synchronous speed at that frequency—
- Poles / nameplate slip—
- Volts per hertz—
- Approximate output voltage—
Show the working
Keep these results
We send this one email through our mail provider and don't keep your address unless you tick the box.
We send this one email through our mail provider and don't keep your address.
How it works
- Ns = 120 × f ÷ Psynchronous speed at the drive frequency
- N ≈ Ns − nameplate slipconstant-torque estimate
- f = (N + slip) × P ÷ 120frequency for a target speed
- V/Hz = V rated ÷ f baseV out ≈ V/Hz × f below base
Worked: 60 Hz, 1750 rpm, 460 V motor run at 45 Hz
- 1750 rpm on 60 Hz is a 4-pole motor (1800 rpm synchronous); nameplate slip = 50 rpm.
- At 45 Hz: Ns = 120 × 45 ÷ 4 = 1350 rpm; shaft ≈ 1350 − 50 = 1300 rpm.
- V/Hz = 460 ÷ 60 = 7.67; output ≈ 7.67 × 45 = 345 V.
Questions people ask
Why does the speed drop a little more than the frequency suggests?
An induction motor always runs below synchronous speed by its slip, and at a given load torque the slip in rpm stays roughly the same as the frequency changes. So at 30 Hz a 1750 rpm motor runs about 900 − 50 = 850 rpm, not half of 1750. This tool uses the nameplate slip as that estimate; a drive in sensorless-vector mode compensates for much of it.
What is volts per hertz?
The ratio of rated voltage to rated frequency — 460 ÷ 60 ≈ 7.67 V/Hz for a 460 V, 60 Hz motor. Keeping that ratio constant keeps the magnetic flux in the motor constant, so it can make full torque at lower speeds without saturating. A drive in V/Hz mode lowers its output voltage in step with frequency below base speed.
What happens above base frequency?
The drive cannot give more than its supply voltage, so above base frequency the voltage stays at rated while the frequency rises. Volts per hertz falls, the flux weakens, and the available torque drops roughly in proportion — the motor is in its constant-horsepower region. Whether the motor and the load are safe at that speed is a question for the motor and machine makers.
Related
- How a VFD works — the lesson behind this tool
- VFD parameters and troubleshooting
- Motor synchronous speed & slip
- Rusty on VFDs?
Spot something wrong on this page? Report it
Thanks — your report was sent.
That didn’t send. Please try again later.
A heads-up on tools that fit — by email, optional
Leave your email and tick the box for a short heads-up, at most every two weeks, about tools, drills and diagrams that fit what you've been working through — here and on bentright.com and fieldcalc.net. One list across the three, one click to leave, and nothing is sent until you confirm from your inbox.