Troisième année Lesson 7 of 13 · about 13 min

Motor starting methods

What you’ll learn

  • Why a motor’s starting current is a problem worth solving, and the trade every reduced-voltage method makes.
  • How across-the-line, primary resistor, autotransformer, wye-delta, soft starter and VFD starts work.
  • How to work the line current and torque each one gives, as a fraction of a full-voltage start.
  • Where each one fits, and where the motor-control labs let you run one.

Before this: Induction motors · Motor control course

At standstill an induction motor draws several times its running current. Every starting method other than across-the-line exists to reduce that surge — and every one that does it by lowering the voltage pays for it in torque, because a motor’s torque falls with the square of its voltage. The drive is the exception, and that is why drives took over.

Across-the-line (direct-on-line)

A contactor connects the motor straight to full voltage. Full starting current, full starting torque, the fastest acceleration, the simplest and cheapest gear. This is the start/stop and seal-in circuit you have already built. It is the right answer for most small motors. It becomes the wrong one when the voltage dip upsets the rest of the building, when the utility limits starting current, or when full torque would snap a belt or hammer a pipe.

The reduced-voltage family

MethodHow it lowers the voltageLine currentStarting torque
Primary resistor (or reactor)Resistors in series with each line, shorted out after a time= the fraction of voltage (e.g. 65%)= fraction² (e.g. 42%)
AutotransformerA tapped autotransformer feeds the motor, then is switched out= tap² (e.g. 42% on 65%)= tap² (e.g. 42%)
Wye-deltaStarts the delta-run windings in wye, then reconnects1/31/3
Part-windingEnergises half of a split winding first, then the restreduced — depends on the motorreduced — depends on the motor
Soft starterSCRs chop the voltage and ramp it upadjustablefalls with voltage²

The autotransformer beats the resistor at the same motor voltage because it is a transformer: stepping the voltage down on the motor side steps the current down on the line side by the same ratio. The resistor just burns the difference.

Across-the-line 100 / 100 Resistor, 65% V 65 / 42 Autotransformer, 65% 42 / 42 Wye-delta 33 / 33 line current torque
Line current (shaded bar) and starting torque (outlined bar) as a percent of an across-the-line start. Figures are the ideal ratios; a real motor’s numbers come from its maker.

Worked: one motor, four starts

  1. A motor draws 600 A locked-rotor across the line (a practice figure) and makes 100% of its locked-rotor torque.
  2. Primary resistor to 65% voltage: 0.65 × 600 = 390 A line current; torque 0.65² = 42%.
  3. Autotransformer, 65% tap: the motor draws 390 A at 65% voltage; the line draws 0.65 × 390 = 253.5 A (42%); torque 42%.
  4. Wye-delta: 600 ÷ 3 = 200 A; torque 33%.
  5. Question the numbers ask: will 33% or 42% of locked-rotor torque still accelerate the load? A fan with its damper closed, yes. A loaded conveyor, maybe not — and a motor that cannot accelerate sits at high current until the overload trips.

Wye-delta in a little more detail

The motor must be built to run in delta on your supply, with both ends of each winding brought out (six leads, or twelve on a dual-voltage motor). The starter connects the windings in wye so each sees 1/√3 of its run voltage; a timer lets the motor come up to speed, then the wye contactor drops and the delta contactor pulls in. Mechanical and electrical interlocks stop both being in at once — that would short the supply. The wye-delta lab has the whole control circuit to run and break.

In an open-transition starter the motor is disconnected for a moment during the switch and drifts out of step with the supply, so reconnecting it causes a spike of current and torque. Closed-transition starters bridge the gap through resistors to smooth it.

Soft starters and drives

A soft starter uses back-to-back SCRs to chop each phase and ramp the voltage up over a set time, often with a current limit. It is smooth and adjustable, and most bypass themselves with a contactor once up to speed. It still lowers torque with voltage — it is a better-behaved resistor starter. A VFD lowers the frequency and voltage together, so the motor starts on the steep part of its speed-torque curve at low speed: near full torque at around rated current. It also controls speed and stopping. The fourth-year VFD lesson picks it up from there.

Sur le chantier

Tips

  • Before changing a starting method, ask what the load needs to break away and accelerate. Less current always comes with less torque (except on a drive).
  • On a wye-delta, confirm the motor is delta-run for your voltage from the nameplate, and match the lead numbers to the maker’s diagram.
  • Set the wye-delta timer so the motor is close to full speed before transition; switching early gives a near full-voltage start anyway.
  • Starter protection and overload settings are code-book and nameplate work, not rules of thumb.

Common mistakes

  • Wiring a wye-delta starter to a motor built to run in wye.
  • Mixing up the lead numbers so one winding is reversed at transition — the motor growls and draws heavy current in delta.
  • Assuming a soft starter gives full torque at low current. That is a drive.
  • Forgetting the interlocks between the wye and delta contactors.
  • Blaming the overload when a reduced-voltage start simply cannot accelerate the load.

Check yourself

0 right of 0 answered 8 questions · pick one answer each

  1. 1.A motor is started wye and then switched to delta. During the wye start, each winding sees what fraction of its run voltage?

  2. 2.Compared with an across-the-line start, a wye-delta start reduces the line current and the starting torque to about…

  3. 3.An autotransformer starter on its 65% tap. How does the LINE current compare with an across-the-line start?

  4. 4.A primary resistor starter drops the motor voltage to 65%. Line current and starting torque are about…

  5. 5.What does a wye-delta starter need from the motor?

  6. 6.Why do reduced-voltage starting methods reduce starting torque?

  7. 7.Which starting method can give full rated torque from standstill while drawing only around rated current from the line?

  8. 8.An open-transition wye-delta starter is known for…

Questions fréquentes

Why not start every motor across the line?

Most small motors are started across the line, and it is the simplest and toughest method. The trouble comes with bigger motors: the starting surge dips the voltage for everything else on the supply, can trip upstream protection, may breach a utility limit, and slams the driven machine (belts, gearboxes, pipes full of water) with full torque. Reduced-voltage starting trades some torque for a gentler start.

Soft starter or VFD?

A soft starter only ramps the voltage up at start (and often down at stop), then usually bypasses itself — cheaper and simpler, but it cannot run the motor at reduced speed and it gives less torque while starting. A VFD controls speed the whole time and gives near-full torque at low current, at a higher price and with harmonics and heat to manage.

Does reduced-voltage starting reduce the energy used?

Not meaningfully. The start lasts seconds. What it reduces is the peak current and the mechanical shock. Energy savings come from running at reduced speed (a VFD on a fan or pump), not from a gentler start.