Transformer full-load current and ratio
Enter the kVA and the two line voltages. You get the full-load current on each side, the line and turns ratios, and — for a three-phase bank — the voltage and current in each winding for the connection you pick.
- Primario: corriente a plena carga—
- Secundario: corriente a plena carga—
- Relación de tensiones—
- Relación de transformación (por devanado)—
- Devanado primario—
- Devanado secundario—
- Secundario, entre línea y neutro—
Mostrar el cálculo
Corriente a plena carga a partir de los kVA de la placa — solo aritmética. El dimensionamiento de conductores y de la protección contra sobrecorriente sale de su libro de código.
Guardar estos resultados
Enviamos este único correo a través de nuestro proveedor de correo y no guardamos su dirección a menos que marque la casilla.
Enviamos este único correo a través de nuestro proveedor de correo y no guardamos su dirección.
How it works
A transformer’s kVA is the same on both sides (less a little loss), so each side’s full-load current is just the kVA divided by that side’s voltage — with the √3 when it is three-phase. Inside a three-phase bank, a wye winding sees the line voltage ÷ √3 and carries the line current; a delta winding sees the full line voltage and carries the line current ÷ √3.
- I = kVA × 1000 ÷ (√3 × V)three-phase, each side
- I = kVA × 1000 ÷ Vsingle-phase
- Wye winding: V ÷ √3, I lineper winding
- Delta winding: V line, I ÷ √3per winding
Worked: 75 kVA, 480 V delta to 208Y/120 V
- Primary: 75,000 ÷ (1.732 × 480) = 90.2 A.
- Secondary: 75,000 ÷ (1.732 × 208) = 208.2 A.
- Line ratio: 480 ÷ 208 = 2.31 : 1. Turns ratio: 480 ÷ 120 = 4 : 1 — the delta winding sees 480 V, the wye winding 120 V.
- Current in each primary (delta) winding: 90.2 ÷ 1.732 = 52.1 A.
Preguntas frecuentes
Why is the secondary current bigger than the primary?
Power in is roughly power out. A step-down transformer lowers the voltage, so to pass the same kVA the current has to go up by the same ratio. A 480-to-208 V transformer carries about 2.3 times the current on its 208 V side — that side is the heavy-current side.
What is the difference between the line ratio and the turns ratio?
The line ratio is line voltage in ÷ line voltage out, what you would read with a meter between lines on each side. The turns ratio is the voltage across one winding on each side — and in a delta-wye bank a wye winding only sees the line voltage ÷ √3. So a 480 V delta to 208Y/120 bank has a line ratio of about 2.31 but a turns ratio of 4:1 (480 across a delta winding, 120 across a wye winding).
Is full-load current the number I size the conductors to?
It is the starting point, not the answer. The conductor, the overcurrent device and any adjustments to them are sized by the rules in your code book, which say what percentage of full-load current to use and in what circumstances. This tool gives you the current; the book turns it into a size.
Ver también
- Three-phase transformer connections — delta-wye, wye-wye and the rest
- Transformer basics — turns ratio and kVA on one pair of coils
- Corriente de falla de un transformador (barra infinita)
- Calculadora de potencia trifásica
- Rusty on transformer connections?
¿Ve algo incorrecto en esta página? Repórtelo
Gracias — su reporte fue enviado.
No se pudo enviar. Vuelva a intentarlo más tarde.
Avisos de herramientas que le sirven — por correo, opcional
Deje su correo y marque la casilla para recibir un aviso breve, como máximo cada dos semanas, sobre herramientas, ejercicios y diagramas que encajan con lo que ha estado estudiando — aquí y en bentright.com y fieldcalc.net. Es la misma lista para los tres, se sale con un clic y no se envía nada hasta que confirme desde su bandeja de entrada.