Tercer año Three-phase · tool
Conversión de impedancia delta ↔ estrella
Enter three impedances in ohms. Delta to wye gives you the three star arms that behave the same between the corners; wye to delta goes the other way. Balanced or not.
- Za—
- Zb—
- Zc—
Mostrar el cálculo
Los tres valores deben ser del mismo tipo (resistencia, o reactancia de un solo signo). La equivalencia vale solo vista desde los tres vértices.
Guardar estos resultados
Enviamos este único correo a través de nuestro proveedor de correo y no guardamos su dirección a menos que marque la casilla.
Enviamos este único correo a través de nuestro proveedor de correo y no guardamos su dirección.
How it works
- Za = Zab × Zca ÷ ΣΔeach wye arm: the two delta sides touching its corner, over the sum
- Zab = ΣP ÷ Zceach delta side: sum of pair products (ZaZb + ZbZc + ZcZa), over the opposite arm
- Balanced: ZY = ZΔ ÷ 3and ZΔ = 3 × ZY
Worked: 10, 20 and 30 Ω in delta
- Sum of the delta: 10 + 20 + 30 = 60 Ω.
- Za (corner A touches Zab and Zca) = 10 × 30 ÷ 60 = 5 Ω.
- Zb (touches Zab and Zbc) = 10 × 20 ÷ 60 = 3.33 Ω.
- Zc (touches Zbc and Zca) = 20 × 30 ÷ 60 = 10 Ω.
- Check between A and B: in the delta it is 10 Ω in parallel with (20 + 30) = 8.33 Ω; in the wye it is Za + Zb = 5 + 3.33 = 8.33 Ω. Same.
Preguntas frecuentes
What is a delta-wye (or pi-tee) conversion for?
It lets you swap three impedances joined in a triangle for three joined in a star (or back) without changing anything measured between the three corners. You use it to untangle a network that is neither series nor parallel — a bridge circuit, a three-phase load you want to treat per phase, or a fault-current study that mixes delta and wye pieces.
Why is a balanced wye one-third of the delta?
When all three are equal, each wye arm works out to Z × Z ÷ 3Z = Z ÷ 3. That is why a balanced delta load can be treated as a wye of one-third the impedance for per-phase arithmetic, using line-to-neutral voltage.
Can I use it for reactances or full impedances?
Yes, as long as all three are the same kind — all resistances, all inductive reactances, or all capacitive reactances. For a mix of resistance and reactance the same formulas apply with complex numbers, which this tool does not do.
Ver también
- Wye and delta: line vs phase
- Calculadora de potencia trifásica
- Series / parallel practice
- Journeyman formula card
¿Ve algo incorrecto en esta página? Repórtelo
Gracias — su reporte fue enviado.
No se pudo enviar. Vuelva a intentarlo más tarde.
Avisos de herramientas que le sirven — por correo, opcional
Deje su correo y marque la casilla para recibir un aviso breve, como máximo cada dos semanas, sobre herramientas, ejercicios y diagramas que encajan con lo que ha estado estudiando — aquí y en bentright.com y fieldcalc.net. Es la misma lista para los tres, se sale con un clic y no se envía nada hasta que confirme desde su bandeja de entrada.