Voltage drop calculator (you enter the resistance)
Type the conductor’s resistance from your code book or the maker’s data, the one-way length, the load current and the supply voltage. You get the drop in volts and percent, and what is left at the load. Nothing here is a code table — that is what keeps it right on any code cycle, CEC or NEC.
Estimación que solo considera la resistencia, con el valor que escribió. Consulte en su libro de código qué resistencia usar y qué caída se permite.
Guardar estos resultados
Enviamos este único correo a través de nuestro proveedor de correo y no guardamos su dirección a menos que marque la casilla.
Enviamos este único correo a través de nuestro proveedor de correo y no guardamos su dirección.
How it works
- VD = 2 × I × R × Lsingle-phase
- VD = √3 × I × R × Lthree-phase, balanced
- % = VD ÷ V × 100against the supply
A conductor is a long, thin resistor. Push current through it and Ohm’s law takes its cut: V = I × R, where R is the resistance per unit length times the length. On a single-phase circuit the current makes the trip twice — out and back — so the length counts twice. R here is per single conductor per unit length, and L is the one-way distance from the source to the load. The result ignores the conductor’s reactance, which is small on branch-circuit sizes and matters more on big feeders; your code book or the maker’s data covers the fuller method.
Worked examples
Single-phase, 100 ft, 16 A on 120 V
- Resistance: say your book gives 2.0 Ω per 1000 ft for the conductor you are using (a round practice number — use your own). Per foot that is 0.002 Ω.
- VD = 2 × 16 × 0.002 × 100 = 6.40 V.
- As a percent: 6.40 ÷ 120 × 100 = 5.33 %, leaving 113.6 V at the load. Compare that with the limit your book sets.
- The same run in metric: 2.0 Ω/1000 ft = 6.562 Ω/km, and 100 ft = 30.48 m. 2 × 16 × 0.006562 × 30.48 = 6.40 V — the same answer, as it must be.
Three-phase, 200 m, 30 A on 600 V
- Practice resistance: 0.5 Ω/km, so 0.0005 Ω per metre.
- VD = 1.732 × 30 × 0.0005 × 200 = 5.20 V.
- 5.196 ÷ 600 × 100 = 0.87 %. On a 208 V system the same drop would be 2.5 % — voltage drop hurts more on lower voltages.
Preguntas frecuentes
Where do I get the resistance number?
From the conductor-properties table in your code book (CSA C22.1 in Canada, the NEC in the US) or the cable maker’s data sheet, for the size, the metal (copper or aluminium) and the temperature you are working at. This site deliberately does not carry that table — it changes by edition, and you should be reading it in your own book.
What percent drop is allowed?
Your code book says, and the limit depends on the kind of circuit and the edition. Type it into the “your limit” box and the calculator tells you whether this run is within it. Treat the number here as arithmetic, not as approval.
Why ×2 for single-phase and ×√3 for three-phase?
On a single-phase circuit the current goes out on one conductor and back on the other, so it crosses the length twice. On a balanced three-phase circuit the return is shared among the other phases, and the line-to-line drop works out to √3 (1.732) times the drop in one conductor.
Ver también
- Voltage drop — the lesson behind this tool.
- Conductors and insulation — the lesson behind this tool.
- Wire length & area converter — feet ↔ metres, AWG ↔ mm².
- Ohm’s law calculator — voltage drop is V = I × R on the wire.
- Ampacity — the other thing a long run is checked for.
- Single & three phase formula sheet
¿Ve algo incorrecto en esta página? Repórtelo
Gracias — su reporte fue enviado.
No se pudo enviar. Vuelva a intentarlo más tarde.
Avisos de herramientas que le sirven — por correo, opcional
Deje su correo y marque la casilla para recibir un aviso breve, como máximo cada dos semanas, sobre herramientas, ejercicios y diagramas que encajan con lo que ha estado estudiando — aquí y en bentright.com y fieldcalc.net. Es la misma lista para los tres, se sale con un clic y no se envía nada hasta que confirme desde su bandeja de entrada.