Rappel pour compagnons Refresher 8 of 10 · about 9 min

Rusty on VFDs?

What you’ll learn

  • The three sections of a drive and the DC-bus voltage to expect.
  • The parameters you set on every drive, and why the nameplate FLA matters.
  • The common trips and what usually causes each one.
  • The two habits that protect you and the drive: bus discharge, and lifting leads before insulation tests.

Before this: How a VFD works

Rectifier AC → DC DC bus 1.35–1.41 × V line Inverter DC → PWM line in to motor stays charged!
Every drive: fixed AC in, a DC bus in the middle, variable-frequency AC out. The bus capacitors hold their charge after the power is off.

Parameters you set on every drive

ParameterFromWhy it matters
Motor voltage, FLA, base Hz, base rpm, powerMotor nameplateMotor overload protection and the motor model
Min / max frequencyThe process and the machine makerKeeps a pump from dead-heading or a fan from overspeeding
Accel / decel timeThe loadToo short: overcurrent on start, overvoltage on stop
Control mode (V/Hz, sensorless vector…)Load typeTorque at low speed; V/Hz for multiple motors on one drive
Start / stop / speed sourceThe control designKeypad, terminals or network — the usual “it won’t start” answer
Stop modeThe processRamp to stop versus coast

The common trips

TripUsual causesFirst check
Overvoltage (DC bus)Decel too fast on a heavy load; high or spiking supplyDecel time; braking resistor; supply voltage
OvercurrentAccel too fast; jammed load; output shortAccel time; load turns freely; insulation (leads lifted)
Ground faultMotor or cable insulation failing; water in a boxInsulation test with leads lifted from the drive
UndervoltageSupply sag or lost phase on the inputThree input voltages, input fuses
Motor overloadReal overload; wrong FLA enteredMotor current vs nameplate; the FLA parameter
Overtemperature (drive)Blocked fan or filter, hot enclosureFans, filters, heat sink, room temperature

Worked check: what should the numbers be?

  1. Drive on 480 V. DC bus at no load ≈ 480 × 1.414 = 679 V; loaded ≈ 480 × 1.35 = 648 V.
  2. Motor: 460 V, 60 Hz, 1770 rpm (4-pole, 1800 synchronous, 30 rpm slip). V/Hz = 460 ÷ 60 = 7.67.
  3. Commanded 40 Hz: output ≈ 7.67 × 40 = 307 V; shaft ≈ 120 × 40 ÷ 4 − 30 = 1200 − 30 = 1170 rpm.

Sur le chantier

Tips

  • Photograph the parameter list (or save it to the keypad or a laptop) before you change anything.
  • The fault history — with the time, current and bus voltage at the trip — is the best clue you will get.
  • Use a true-RMS meter with a low-pass (drive) setting on the output side.

Common mistakes

  • Meggering a motor with the drive still connected.
  • Touching the bus terminals because the display is dark.
  • Shortening decel to fix a slow stop and getting overvoltage trips instead.
  • Running a TEFC motor slowly for long periods without checking it can cool itself.

Check yourself

0 right of 0 answered 6 questions · pick one answer each

  1. 1.A drive trips on DC-bus overvoltage every time the machine is stopped. The most likely cause?

  2. 2.Roughly what DC-bus voltage do you expect on a 480 V drive with the motor stopped (light load)?

  3. 3.A 460 V, 60 Hz motor on a drive in V/Hz mode is running at 30 Hz. About what voltage is the drive putting out?

  4. 4.Which nameplate data should be entered into a drive before the first run?

  5. 5.An instant overcurrent or ground-fault trip right at start, even with a long accel time. What do you check first?

  6. 6.Why is a contactor between a running drive and its motor a problem?

Questions fréquentes

Why does the drive show a different current than my clamp meter?

The output of a drive is a chopped (PWM) waveform. An average-responding clamp can read it badly; a true-RMS meter with a low-pass filter setting made for drive outputs reads it properly. The input current is different again, because the rectifier draws current in pulses.

Can I run a motor above 60 Hz on a drive?

The drive can; whether the motor and the machine can is a question for their makers. Above base frequency the drive holds the voltage at rated, so torque capability falls, and the mechanical speed limit of the motor and the driven load matters.

How long do I wait after power-off before touching a drive?

As long as the drive label and manual say — often several minutes — and then prove the DC bus dead with a meter. The capacitors hold a lethal charge after the display goes dark.