Rappel pour compagnons Refresher 10 of 10 · about 5 min

Journeyman formula card

What you’ll learn

  • Every formula from the third-year, fourth-year and refresher material on one page.
  • Which variable is which — line or phase, per winding or per line.
  • A tool and a lesson for each group, when you need the working or the why.

Puissance triphasée

kVA = √3 × V × I ÷ 1000V line-to-line, I line
kW = kVA × PFreal power
kVAR = √(kVA² − kW²)reactive power
I = kW × 1000 ÷ (√3 × V × PF)current from kW
Wye: V L = √3 × V ph, I L = I phDelta: V L = V ph, I L = √3 × I ph

Open the tool · Read the lesson

Transformers

FLA = kVA × 1000 ÷ (√3 × V)three-phase, each side
FLA = kVA × 1000 ÷ Vsingle-phase
Turns ratio = V winding pri ÷ V winding secper winding, not line to line
Open delta ≈ 57.7% of the three-can bank1 ÷ √3

Open the tool · Read the lesson

Available fault current

Isc = FLA × 100 ÷ %Zinfinite bus, at the terminals
Multiplier = 100 ÷ %Ze.g. 5% → 20 × FLA

Open the tool · Read the lesson

Motors

Ns = 120 × f ÷ Psynchronous speed, rpm
Slip % = (Ns − N) ÷ Ns × 100N = actual speed
f rotor = slip × frotor current frequency
I = HP × 746 ÷ (√3 × V × eff × PF)three-phase current from HP (use the nameplate for real work)

Open the tool · Read the lesson

Drives

V/Hz = V rated ÷ f baseheld constant below base
N ≈ 120 × f ÷ P − slip rpmshaft speed on a drive
DC bus ≈ 1.35 to 1.41 × V lineloaded to no-load

Open the tool · Read the lesson

Correction du FP

kVAR = kW × (tan φ1 − tan φ2)φ = arccos PF
C = Q ÷ (2π f V²)per capacitor; Q in VAR, V across it

Open the tool · Read the lesson

Déséquilibre de tension

% = max deviation from average ÷ average × 100three line-to-line readings

Open the tool · Read the lesson

4–20 mA

PV = LRV + (mA − 4) ÷ 16 × spancurrent to value
mA = 4 + 16 × (PV − LRV) ÷ spanvalue to current
V = I × R4–20 mA × 250 Ω = 1–5 V

Open the tool · Read the lesson

Delta ↔ wye impedance

Za = Zab × Zca ÷ (Zab + Zbc + Zca)delta to wye
Zab = (ZaZb + ZbZc + ZcZa) ÷ Zcwye to delta
Balanced: Z wye = Z delta ÷ 3

Open the tool · Read the lesson

Worked check: three formulas on one motor

  1. 10 HP, 460 V, eff 0.90, PF 0.85: I = 10 × 746 ÷ (1.732 × 460 × 0.90 × 0.85) = 7,460 ÷ 609.5 = 12.2 A (a physics estimate — the nameplate FLA is what you use).
  2. Nameplate speed 1760 rpm on 60 Hz: 4-pole, Ns 1800, slip = 40 ÷ 1800 = 2.2%.
  3. On a drive at 50 Hz: shaft ≈ 120 × 50 ÷ 4 − 40 = 1460 rpm; output ≈ 460 ÷ 60 × 50 = 383 V.

Sur le chantier

Tips

  • Print it double-sided and keep it with your code book tabs while you study.
  • Before using a formula, say out loud what V and I it wants — line or phase.
  • Work each answer back the other way; a formula that does not close was used wrong.

Common mistakes

  • Using 3 instead of √3 with line values.
  • Using the line ratio as the turns ratio on a delta–wye bank.
  • Dividing by %Z as a whole number without the 100 (5 instead of 0.05).
  • Using a calculated motor current where your code book tells you to use its own values.

Check yourself

0 right of 0 answered 5 questions · pick one answer each

  1. 1.What is the synchronous speed of a 6-pole motor on 60 Hz?

  2. 2.A 300 kVA transformer with 5% impedance and a 208 V secondary. Infinite-bus fault current at its terminals?

  3. 3.A 4–20 mA pressure transmitter is ranged 0–100 psi. What does 8 mA represent?

  4. 4.kVAR to correct a 50 kW load from PF 0.80 to 0.95?

  5. 5.Three equal 12 Ω impedances in delta. The equivalent wye has arms of…