Rappel pour compagnons Refresher 2 of 10 · about 9 min
Rusty on three-phase math?
What you’ll learn
- Which of voltage or current carries the √3 in a wye and in a delta.
- The power formula and the current formula, both directions, with the right voltage.
- The power triangle — kW, kVA, kVAR — without drawing it.
- Quick sanity checks that catch a slipped √3 before it reaches a panel.
Before this: Wye and delta
Line and phase, in one table
| Wye (star) | Triangle | |
|---|---|---|
| Tension | V line = √3 × V phase | V line = V phase |
| Courant | I line = I phase | I line = √3 × I phase |
| Neutral? | Yes — the centre point | No (a high-leg delta taps one winding) |
| Everyday pairs | 208Y/120, 480Y/277, 600Y/347 | 240 V, 480 V, 600 V delta |
The formulas you actually use
- kVA = √3 × V × I ÷ 1000line-to-line V, line I
- kW = kVA × PFreal power
- I = kW × 1000 ÷ (√3 × V × PF)current from kW
- I = kVA × 1000 ÷ (√3 × V)current from kVA
- kVAR = √(kVA² − kW²)reactive power
- √3 × V LL = 3 × V LNwhy both forms agree
Worked check: both directions
- A 208 V three-phase load draws 50 A per line at PF 0.85. kVA = 1.732 × 208 × 50 ÷ 1000 = 18.0 kVA.
- kW = 18.0 × 0.85 = 15.3 kW. kVAR = √(18.0² − 15.3²) = 9.5 kVAR.
- Now back: I = 15,300 ÷ (1.732 × 208 × 0.85) = 15,300 ÷ 306.2 = 50.0 A. It closes — that is the check.
- Same load worked with phase values: 3 × 120 × 50 × 0.85 = 15,300 W. Same answer, as it should be.
Sanity checks
- Line voltage on a wye is always the bigger number. If you divided to get it, you went the wrong way.
- At the same kW, three-phase current is lower than single-phase current at the same voltage by 1.732.
- Rough rule on 600 V: about 1 A per kVA (1000 ÷ (1.732 × 600) = 0.96). On 480 V: about 1.2 A per kVA. On 208 V: about 2.8 A per kVA.
- A lower power factor always means more current for the same kW, never less.
Sur le chantier
Tips
- Carry the amps-per-kVA figure for the voltages you work on — it checks a nameplate in your head.
- When the numbers do not close, work them backwards. A formula applied twice in opposite directions should return what you started with.
- Write the unit on every line. kVA, kW and kVAR mixed up are the usual slip.
Common mistakes
- Using line-to-neutral voltage with √3 (or line-to-line with 3).
- Putting the √3 on current in a wye or on voltage in a delta.
- Adding kW and kVAR to get kVA.
- Forgetting the power factor when going from kW to amps.
Check yourself
-
1.A balanced three-phase heater draws 40 A per line at 600 V. Roughly how many kW is it?
kW = √3 × V × I × PF ÷ 1000 = 1.732 × 600 × 40 × 1.0 ÷ 1000 = 41.6 kW. 24 kW forgets the √3; 72 kW uses 3 instead of √3 with line values.
-
2.A 30 kW three-phase load at 0.9 PF on 480 V. What is the line current?
I = kW × 1000 ÷ (√3 × V × PF) = 30,000 ÷ (1.732 × 480 × 0.9) = 30,000 ÷ 748.2 = 40.1 A. 36.1 A would be the answer at PF 1.0 — a poor power factor always raises the current for the same kW.
-
3.On a 480Y/277 system, what is the voltage from any line to neutral?
Line to neutral on a wye is the line voltage ÷ √3: 480 ÷ 1.732 = 277 V.
-
4.A balanced delta load has 20 A in each winding. What is the line current?
In a delta the line current is √3 × the winding (phase) current: 20 × 1.732 = 34.6 A.
-
5.The three-phase formula uses √3 × V × I. What V and I does it expect?
The √3 is there precisely because you are using line values — what you can measure. If you use line-to-neutral volts instead, the formula becomes 3 × V phase × I.
-
6.A load is 100 kVA at 0.8 PF. What are its kW and kVAR?
kW = kVA × PF = 80. kVAR = √(100² − 80²) = √3600 = 60. The power triangle is a 3-4-5 right triangle here — kW and kVAR do not simply add up to kVA.
Questions fréquentes
When do I use √3 and when do I use 3?
Use √3 with line-to-line voltage and line current: P = √3 × V LL × I × PF. Use 3 with line-to-neutral (phase) voltage: P = 3 × V LN × I × PF. They give the same answer on a balanced load, because V LL = √3 × V LN.
Is 1.732 accurate enough?
Yes. √3 is 1.73205…; 1.732 gets you within a hundredth of a percent, which is far better than any meter reading you will put into the formula.
What if the load is unbalanced?
For a small imbalance, average the three line currents and use the balanced formula. For a large one, work each phase on its own (V LN × I × PF) and add the three. The neutral current on a wye is a separate question — see the unbalanced-loads lesson.
Voir aussi
- Wye and delta: line vs phase — the full lesson
- Three-phase power and power factor — the full lesson
- Unbalanced loads and neutral current
- Calculateur de puissance triphasée
- Journeyman formula card — every formula, printable
- Single & three phase formula sheet
Vous voyez une erreur sur cette page? Signalez-la
Merci — votre signalement a été envoyé.
L’envoi n’a pas fonctionné. Veuillez réessayer plus tard.
Un petit mot sur les outils qui vous conviennent — par courriel, facultatif
Laissez votre courriel et cochez la case pour un petit mot, au plus toutes les deux semaines, sur les outils, exercices et schémas qui vont avec ce que vous étudiez — ici et sur bentright.com et fieldcalc.net. Une seule liste pour les trois, un clic pour la quitter, et rien n’est envoyé avant que vous confirmiez depuis votre boîte de réception.