Troisième année Three-phase · tool

Calculateur de puissance triphasée

Enter the line-to-line voltage, the power factor and any one of current, kW or kVA. The rest — and the kVAR — are worked out with the √3 formula, and the working is shown with your numbers.

Source
Je connais…
  • Courant de ligne—
  • Puissance apparente—
  • Puissance active—
  • Puissance réactive—
  • Angle de déphasage (en retard)—
Voir le calcul détaillé

    Arithmétique sur les chiffres que vous avez entrés, pour une charge équilibrée. L’outil ne dimensionne rien — les conducteurs et la protection relèvent de votre Code.

    Garder ces résultats

    Nous envoyons ce seul courriel par notre fournisseur de courriel et ne gardons pas votre adresse.

    How it works

    Three quantities describe the power in an AC circuit. kVA (apparent power) is volts times amps — what the wires and the transformer have to carry. kW (real power) is the part that does work: heat, light, a turning shaft. kVAR (reactive power) is the part that sloshes back and forth building magnetic fields in motors and transformers. They form a right triangle, and the power factor is kW ÷ kVA.

    • kVA = √3 × V × I ÷ 1000three-phase, line values
    • kVA = V × I ÷ 1000single-phase
    • kW = kVA × PFreal power
    • kVAR = √(kVA² − kW²)reactive power
    • I = kW × 1000 ÷ (√3 × V × PF)three-phase current from kW

    Worked: the default numbers

    1. 480 V three-phase, 100 A per line, power factor 0.85.
    2. kVA = 1,732 × 480 × 100 ÷ 1000 = 83,1 kVA.
    3. kW = 83,1 × 0,85 = 70,7 kW.
    4. kVAR = √(83.1² − 70.7²) = 43.8 kVAR. The angle whose cosine is 0.85 is 31.8°.

    Motor loads are where the power factor matters: the same 70.7 kW at a power factor of 1.0 would need only 85 A. The extra 15 A is the reactive current, and it heats the conductors just as much as the useful current does — the subject of the power factor correction tool.

    Questions fréquentes

    Why is there a √3 in the three-phase power formula?

    Because the line voltage of a three-phase system is √3 times the voltage across one phase of a wye, and the three phases each carry their share. Written in line values — the ones you can actually measure — the total comes out as √3 × V line × I line. It is the same power as three single-phase circuits, just expressed in the numbers on your meter.

    Should I use line-to-line or line-to-neutral voltage?

    Line-to-line (208, 480, 600…) in the √3 formula, with the current in one line. If you only have line-to-neutral figures you can use 3 × V phase × I instead — it gives the same answer on a balanced load.

    What if the three line currents are different?

    The formula assumes a balanced load. For a modest imbalance, using the average of the three currents gets you close. For a badly unbalanced load, work each phase separately (V line-to-neutral × I × PF for each) and add them.

    Where do I get the power factor?

    From the equipment (a motor nameplate or data sheet gives it at full load), from a power-quality meter, or from the utility bill for a whole building. Resistive heat and incandescent lighting are 1.0. If you do not know it, the kVA and amps are still right — only the kW and kVAR need the PF.

    Voir aussi

    Vous voyez une erreur sur cette page? Signalez-la

    Nous joindrons cette page et les nombres que vous avez tapés. Nous lisons chaque signalement, mais nous ne pouvons pas y répondre.

    Merci — votre signalement a été envoyé.

    L’envoi n’a pas fonctionné. Veuillez réessayer plus tard.