Three-phase power calculator
Enter the line-to-line voltage, the power factor and any one of current, kW or kVA. The rest — and the kVAR — are worked out with the √3 formula, and the working is shown with your numbers.
- Current per line—
- Apparent power—
- Real power—
- Reactive power—
- Phase angle (lagging)—
Show the working
Arithmetic on the numbers you entered, assuming a balanced load. It sizes nothing — conductors and protection come from your code book.
Keep these results
We send this one email through our mail provider and don't keep your address unless you tick the box.
We send this one email through our mail provider and don't keep your address.
How it works
Three quantities describe the power in an AC circuit. kVA (apparent power) is volts times amps — what the wires and the transformer have to carry. kW (real power) is the part that does work: heat, light, a turning shaft. kVAR (reactive power) is the part that sloshes back and forth building magnetic fields in motors and transformers. They form a right triangle, and the power factor is kW ÷ kVA.
- kVA = √3 × V × I ÷ 1000three-phase, line values
- kVA = V × I ÷ 1000single-phase
- kW = kVA × PFreal power
- kVAR = √(kVA² − kW²)reactive power
- I = kW × 1000 ÷ (√3 × V × PF)three-phase current from kW
Worked: the default numbers
- 480 V three-phase, 100 A per line, power factor 0.85.
- kVA = 1.732 × 480 × 100 ÷ 1000 = 83.1 kVA.
- kW = 83.1 × 0.85 = 70.7 kW.
- kVAR = √(83.1² − 70.7²) = 43.8 kVAR. The angle whose cosine is 0.85 is 31.8°.
Motor loads are where the power factor matters: the same 70.7 kW at a power factor of 1.0 would need only 85 A. The extra 15 A is the reactive current, and it heats the conductors just as much as the useful current does — the subject of the power factor correction tool.
Questions people ask
Why is there a √3 in the three-phase power formula?
Because the line voltage of a three-phase system is √3 times the voltage across one phase of a wye, and the three phases each carry their share. Written in line values — the ones you can actually measure — the total comes out as √3 × V line × I line. It is the same power as three single-phase circuits, just expressed in the numbers on your meter.
Should I use line-to-line or line-to-neutral voltage?
Line-to-line (208, 480, 600…) in the √3 formula, with the current in one line. If you only have line-to-neutral figures you can use 3 × V phase × I instead — it gives the same answer on a balanced load.
What if the three line currents are different?
The formula assumes a balanced load. For a modest imbalance, using the average of the three currents gets you close. For a badly unbalanced load, work each phase separately (V line-to-neutral × I × PF for each) and add them.
Where do I get the power factor?
From the equipment (a motor nameplate or data sheet gives it at full load), from a power-quality meter, or from the utility bill for a whole building. Resistive heat and incandescent lighting are 1.0. If you do not know it, the kVA and amps are still right — only the kW and kVAR need the PF.
Related
- Three-phase power and power factor — the lesson behind this tool
- Wye and delta: line vs phase
- Power factor correction calculator
- Transformer full-load current & ratio
- Single & three phase formula sheet
Spot something wrong on this page? Report it
Thanks — your report was sent.
That didn’t send. Please try again later.
A heads-up on tools that fit — by email, optional
Leave your email and tick the box for a short heads-up, at most every two weeks, about tools, drills and diagrams that fit what you've been working through — here and on bentright.com and fieldcalc.net. One list across the three, one click to leave, and nothing is sent until you confirm from your inbox.