Journeyman refresher Refresher 2 of 10 · about 9 min

Rusty on three-phase math?

What you’ll learn

  • Which of voltage or current carries the √3 in a wye and in a delta.
  • The power formula and the current formula, both directions, with the right voltage.
  • The power triangle — kW, kVA, kVAR — without drawing it.
  • Quick sanity checks that catch a slipped √3 before it reaches a panel.

Before this: Wye and delta

Line and phase, in one table

Wye (star)Delta
VoltageV line = √3 × V phaseV line = V phase
CurrentI line = I phaseI line = √3 × I phase
Neutral?Yes — the centre pointNo (a high-leg delta taps one winding)
Everyday pairs208Y/120, 480Y/277, 600Y/347240 V, 480 V, 600 V delta
kW (real) kVAR kVA φ PF = cos φ = kW ÷ kVA
The power triangle. kVA is the long side, so kW and kVAR never add up to it directly — kVA² = kW² + kVAR².

The formulas you actually use

  • kVA = √3 × V × I ÷ 1000line-to-line V, line I
  • kW = kVA × PFreal power
  • I = kW × 1000 ÷ (√3 × V × PF)current from kW
  • I = kVA × 1000 ÷ (√3 × V)current from kVA
  • kVAR = √(kVA² − kW²)reactive power
  • √3 × V LL = 3 × V LNwhy both forms agree

Worked check: both directions

  1. A 208 V three-phase load draws 50 A per line at PF 0.85. kVA = 1.732 × 208 × 50 ÷ 1000 = 18.0 kVA.
  2. kW = 18.0 × 0.85 = 15.3 kW. kVAR = √(18.0² − 15.3²) = 9.5 kVAR.
  3. Now back: I = 15,300 ÷ (1.732 × 208 × 0.85) = 15,300 ÷ 306.2 = 50.0 A. It closes — that is the check.
  4. Same load worked with phase values: 3 × 120 × 50 × 0.85 = 15,300 W. Same answer, as it should be.

Sanity checks

  • Line voltage on a wye is always the bigger number. If you divided to get it, you went the wrong way.
  • At the same kW, three-phase current is lower than single-phase current at the same voltage by 1.732.
  • Rough rule on 600 V: about 1 A per kVA (1000 ÷ (1.732 × 600) = 0.96). On 480 V: about 1.2 A per kVA. On 208 V: about 2.8 A per kVA.
  • A lower power factor always means more current for the same kW, never less.

On the job

Tips

  • Carry the amps-per-kVA figure for the voltages you work on — it checks a nameplate in your head.
  • When the numbers do not close, work them backwards. A formula applied twice in opposite directions should return what you started with.
  • Write the unit on every line. kVA, kW and kVAR mixed up are the usual slip.

Common mistakes

  • Using line-to-neutral voltage with √3 (or line-to-line with 3).
  • Putting the √3 on current in a wye or on voltage in a delta.
  • Adding kW and kVAR to get kVA.
  • Forgetting the power factor when going from kW to amps.

Check yourself

0 right of 0 answered 6 questions · pick one answer each

  1. 1.A balanced three-phase heater draws 40 A per line at 600 V. Roughly how many kW is it?

  2. 2.A 30 kW three-phase load at 0.9 PF on 480 V. What is the line current?

  3. 3.On a 480Y/277 system, what is the voltage from any line to neutral?

  4. 4.A balanced delta load has 20 A in each winding. What is the line current?

  5. 5.The three-phase formula uses √3 × V × I. What V and I does it expect?

  6. 6.A load is 100 kVA at 0.8 PF. What are its kW and kVAR?

Questions people ask

When do I use √3 and when do I use 3?

Use √3 with line-to-line voltage and line current: P = √3 × V LL × I × PF. Use 3 with line-to-neutral (phase) voltage: P = 3 × V LN × I × PF. They give the same answer on a balanced load, because V LL = √3 × V LN.

Is 1.732 accurate enough?

Yes. √3 is 1.73205…; 1.732 gets you within a hundredth of a percent, which is far better than any meter reading you will put into the formula.

What if the load is unbalanced?

For a small imbalance, average the three line currents and use the balanced formula. For a large one, work each phase on its own (V LN × I × PF) and add the three. The neutral current on a wye is a separate question — see the unbalanced-loads lesson.