Fourth year Protection · tool
Transformer fault current (infinite-bus estimate)
Enter the transformer kVA, secondary voltage and nameplate %Z. The tool gives the full-load current and the most current a bolted fault at the secondary terminals could draw if the supply behind it were infinitely stiff.
- Secondary full-load current—
- Multiplier (100 ÷ %Z)—
- Fault current at the secondary terminals (infinite bus)—
Show the working
Worst-case estimate: the real fault current is lower once the utility and conductor impedance are counted. Equipment ratings and the study itself come from your code book and the engineer of record.
Keep these results
We send this one email through our mail provider and don't keep your address unless you tick the box.
We send this one email through our mail provider and don't keep your address.
How it works
- FLA = kVA × 1000 ÷ (√3 × V)three-phase (÷ V alone for single-phase)
- Multiplier = 100 ÷ %Ztimes full-load current
- Isc = FLA × 100 ÷ %Zbolted fault, infinite bus
Worked: 500 kVA, 480 V, 5.75 %Z
- FLA = 500,000 ÷ (1.732 × 480) = 601 A.
- Multiplier = 100 ÷ 5.75 = 17.39.
- Isc = 601 × 17.39 = about 10,460 A at the terminals, before any conductor or utility impedance.
Questions people ask
What does "infinite bus" mean?
It assumes the utility behind the transformer is infinitely strong — it can supply any current without its voltage sagging — so the only thing limiting a fault is the transformer’s own impedance. Real supplies are not infinite, so the real fault current is lower. That makes this the worst case at the transformer terminals, which is the useful number for a first look.
Why does a lower %Z give a bigger fault current?
%Z is the percentage of rated voltage it takes to push full-load current through the transformer with its secondary shorted. A 5% transformer reaches full-load current with only 5% voltage applied, so at 100% voltage it would pass 100 ÷ 5 = 20 times full-load current into a bolted fault. Halve the %Z and you double the fault current.
Why is there a tolerance field?
The %Z on the plate is a measured or design value with a manufacturing tolerance — the actual unit may be a little lower. Some engineers allow for that by using a slightly lower %Z, which gives a slightly higher (more conservative) fault current. Enter the tolerance you have been told to use, or leave it at 0.
Is this the number for the panel down the hall?
No. Every metre or foot of conductor adds impedance and lowers the fault current further downstream. Point-to-point methods and study software add those impedances in. The equipment interrupting and withstand ratings needed at each point are an engineering and code-book question.
Related
- Available fault current — the lesson behind this tool
- Transformer full-load current & ratio
- Overcurrent protection and coordination
- Protective relaying concepts
Spot something wrong on this page? Report it
Thanks — your report was sent.
That didn’t send. Please try again later.
A heads-up on tools that fit — by email, optional
Leave your email and tick the box for a short heads-up, at most every two weeks, about tools, drills and diagrams that fit what you've been working through — here and on bentright.com and fieldcalc.net. One list across the three, one click to leave, and nothing is sent until you confirm from your inbox.