Fourth year Power quality · tool
Voltage unbalance calculator
Enter three line-to-line voltage readings (or three line currents). The tool gives the average, the largest deviation from it, and the percent unbalance — and for voltages, the negative-sequence unbalance too.
- Average—
- Largest deviation from average—
- Unbalance (max deviation ÷ average)—
- Negative-sequence unbalance—
Show the working
Arithmetic on your three readings. What unbalance a motor can take, and how much to derate it, comes from the motor maker’s data.
Keep these results
We send this one email through our mail provider and don't keep your address unless you tick the box.
We send this one email through our mail provider and don't keep your address.
How it works
- Average = (A + B + C) ÷ 3of the three readings
- % = max |reading − avg| ÷ avg × 100the field definition
- VUF = V negative ÷ V positive × 100sequence method, from line-to-line magnitudes
Worked: 460, 467 and 450 V
- Average = (460 + 467 + 450) ÷ 3 = 459 V.
- Deviations: 1, 8 and 9 V. The largest is 9 V (the 450 reading).
- Unbalance = 9 ÷ 459 × 100 = 1.96%.
- On a motor, expect the current unbalance to be several times that — measure it and compare.
Questions people ask
Why does a small voltage unbalance matter to a motor?
An unbalanced supply contains a small negative-sequence voltage — a component trying to turn the motor backwards. The motor’s impedance to it is low, so a few percent of voltage unbalance drives a much larger percentage of current unbalance, and that extra current is pure heat in the windings. Motor makers publish how much a motor must be derated for a given unbalance.
Should I measure line-to-line or line-to-neutral?
Line-to-line for a three-phase motor — that is what the motor sees, and it is what the negative-sequence figure here is built for. The percent-deviation method works with either, as long as all three readings are the same kind.
What is the difference between the two percentages?
The first is the common field definition: the largest difference from the average, divided by the average. The second is the "true" unbalance — the negative-sequence voltage as a percentage of the positive-sequence voltage — calculated from the three line-to-line readings. For small unbalances they come out close; the field figure is the one most motor data is written against.
Where does unbalance come from?
Single-phase loads spread unevenly across the phases, a blown fuse in a capacitor bank, a bad connection or a high-resistance contact on one leg, an open-delta supply, or unequal transformer taps. Find it by measuring at points going upstream until the unbalance disappears.
Related
- Unbalanced loads and neutral current
- Power quality and harmonics
- Motor troubleshooting flowcharts — runs hot? check this first
- Using a multimeter
Spot something wrong on this page? Report it
Thanks — your report was sent.
That didn’t send. Please try again later.
A heads-up on tools that fit — by email, optional
Leave your email and tick the box for a short heads-up, at most every two weeks, about tools, drills and diagrams that fit what you've been working through — here and on bentright.com and fieldcalc.net. One list across the three, one click to leave, and nothing is sent until you confirm from your inbox.